High-Voltage Metering Box (JLSZV-10)

High-voltage metering box (combined instrument transformer).

The JLSZV-10 high-voltage metering box, also known as a combined instrument transformer, is suitable for outdoor installation and can be used for both metering and measurement. It is used for active and reactive energy metering in AC 50Hz three-phase power lines with a rated voltage of 6kV or 10kV. It is suitable for high-voltage energy metering at lines, substation outlets, industrial, commercial, and dedicated transformer users.

This metering device complies with the provisions and requirements of national standards GB20840.4-2015 “Supplementary Technical Requirements for Combined Instrument Transformers”, GB20840.2-2014 “Current Transformers”, and GB20840.3-2013 “Supplementary Technical Requirements for Voltage Transformers”.

Share

Product Model Description

JLSZV-10

JL: Voltage and Current Combination

S: Three-phase

Z: Cast-in-place Insulation

V: Wiring Method V-type

10: Rated Voltage

Product Features

1. This combined instrument transformer is epoxy resin cast, fully enclosed, and has a pillar-type structure.

2. Utilizing outdoor epoxy resin casting, the product features arc resistance, UV resistance, aging resistance, long lifespan, and maintenance-free operation.

3. Employing epoxy resin insulation and a rainproof umbrella-skirt pillar-type structure, it boasts a large creepage distance and strong anti-pollution flashover capability.

4. This product consists of two single-phase fully insulated voltage transformers connected in a “V” configuration, with two current transformers connected in series on phases A and C respectively. The secondary windings of the current transformers have taps to achieve different current ratios.

5. Replacing traditional oil-immersed combined instrument transformers, it can be installed in any orientation and operates maintenance-free for extended periods.

6. The multi-ratio current structure can meet the capacity expansion requirements of the system load, offering greater economic benefits.

Main technical parameters

NameParameter
Rated Voltage6kV, 10kV
Rated Current5~600A
Voltage Transformer Capacity20VA
Current Transformer Capacity10VA
Rated Secondary Voltage of Metering Circuit100V or 100/√3V
Rated Secondary Current of Metering Circuit5A
Accuracy VoltageTransformer 0.2 class, Current Transformer 0.2S class
Rated Power Frequency Withstand Voltage (1min)42kV
Withstand Lightning Impulse Voltage (Peak)75kV

Customers who bought this, also loved

评价

目前还没有评价

成为第一个“High-Voltage Metering Box (JLSZV-10)” 的评价者